4000A Outdoor Sandwich type
Aluminium LT Busduct |
|
- |
|
Supply, Installation, Testing and Commissioning of
4000 Amps 4Pole Outdoor Type 50KA, 415V, 3Phase, 4wire, 50Hz A.C Sandwich type Aluminium busduct with suitable support
as per the Technical specifications. The busduct should be with straight run,
90 deg. Horizontal and vertical bends., busbar trunking fittings (elbow,
tees, end caps, End feed Box, end covers, horizontal fixing devices,etc.) The busduct shall run from Transformer-1 & 2 secondary side
to the MPCC Incoming side. Horizontal runs of busbar
trunking system shall be supported by hangers at every 2 metre. Vertical runs
of busbar trunking system shall be supported by hangers not more than 4m
apart.Busbar trunking system shall be terminated by Œend caps(closure)¹ |
30 |
- |
2 |
4000A Indoor Sandwich type Aluminium LT
Busduct |
|
- |
|
Supply, Installation, Testing and Commissioning of
4000 Amps 4pole Indoor Type 50KA, 415V, 3Phase, 4wire, 50Hz A.C Sandwich type Aluminium busduct with
suitable support as per the Technical specifications. The busduct should be
with straight run, 90 deg. Horizontal and vertical bends., busbar trunking
fittings (elbow, tees, end caps, End feed Box, end covers, horizontal fixing
devices,etc.) The busduct shall run from
Transformer-1 & 2 secondary side to the MPCC Incoming side and from
Generator AMF, Auto Load sharing/Synchronising Panel to the MPCC Incoming
side. Horizontal runs of busbar trunking system
shall be supported by hangers at every 2 metre. Vertical runs of busbar
trunking system shall be supported by hangers not more than 4m apart.Busbar
trunking system shall be terminated by Œend caps(closure)¹. |
90 |
- |
3 |
4000A Flexible Joints |
|
- |
|
Supply,Fixing, Testing and Commissioning of
4000Amps 4Pole flexible joints suitable for Sandwich type
Aluminium bus duct including all required necessary
accessories. |
24 |
- |
4 |
2500A Indoor Sandwich type Aluminium LT Busduct for APFCC Capacitor Panel - 1 & 2 |
|
- |
|
Supply, Installation, Testing and Commissioning of
2500 Amps 4Pole indoor type 50KA, 415V, 3Phase, 4wire, 50Hz A.C Sandwich type Aluminium busduct with suitable support
as per the Technical specifications enclosed. The busduct should be with
straight run, 90 deg. Horizontal and vertical bends., busbar trunking
fittings (elbow, tees, end caps,End (Cable) feed Box, end covers, horizontal
fixing devices,etc.) The busduct
shall run from MPCC to APFCC Capacitor panel 1&
2. Horizontal runs of busbar trunking system shall
be supported by hangers at every 2 metre. Vertical runs of busbar trunking
system shall be supported by hangers not more than 4m apart. Busbar trunking
system shall be terminated by Œend caps(closure)¹. |
20 |
- |
5 |
2500A Flexible Joints |
|
- |
|
Supply,Fixing, Testing and Commissioning of 2500Amps
4Pole flexible joints suitable for sandwich type Aluminium
bus duct including all required necessary accessories. |
4 |
- |
6 |
Main Power Control Centre |
|
- |
|
Supply, Installation , Testing and Commissioning of
415V, 3Phase, 50Hz, 4wire A.C system sheet steel clad dust and vermin proof
of Cubicle type, Indoor type, floor mounting, free standing, extendible type
Main Power Control Centre compartmentalized design and fabricated made out
of 2mm CRCA sheet steel for main frame, folded sections and load bearing
members and 1.6mm CRCA sheet steel for doors & covers and MS channel
(75x40mm) and removable Gland Plate at bottom entries complete with 4000A Aluminium busbars, single busbar
system, Interconnections, cable chamber, powder coated painting, earthing
etc., with Electrical interlocks as per the various status of 4Nos of
Incomers ( 2Nos from Transformers & 2Nos from Generator AMF, Auto Load
Sharing/ Synchronysing Control Panel ) and 1No of Buscoupler as mentioned in
the BOQ/Specifications/Schematic Diagrams. |
|
- |
|
Providing and fixing of following switchgear
arrangements, components complete with 2Nos of seperate earth busbar
throughout a length of the panel, terminal arrangement for bus trunking at
bottom/top entries for Incomers/Outgoings and also outgoing terminations for
various sizes of cables for Incoming and Outgoing feeders shall be
accommodated in a modular multi tier arrangements, adequate size cable alley,
sign writing, painting earthing, numbering, danger plates etc., complete with
all necessary required accessories as per the detailed Technical
Specifications and Drawings enclosed comprising of the following: |
|
- |